Please note if package is open or product has been used there will be no return allowed NO EXCEPTIONS Thanks 
Description
Product Overview:
 Combination gas control for use in 24 Vac, gas-fired, intermittent pilot appliances with capacities from 30 to 415 cfh 
Product Features:
 Controls include safety shutoff, manual valve, two automatic operators, pressure regulator and pilot adjustment
 Use with S86F,H; S860D; S8600F,H; S8610 and S90A,B Control Modules
 Compact size
 Provide two automatic valves - Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends, Diaphragm-operated second automatic valve opens under control of regulator; closes if gas or power supply is interrupted
 Meets codes requiring dual safety shutoff
 Natural to LP and LP to Natural conversion kits available for standard and slow opening gas valves
 All adjustments, wiring connections and pilot outlet are accessible from top of control
 Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure
 Compatible with ECO connector
 ON-OFF lighting sequence 
Product Specifications:
 Description: 24 Vac Dual Intermittent Pilot, Slow Opening Gas Valve with 3/4 in. x 3/4 in. inlet/oulet, standard opening and 3.5 in. wc pressure regulator setting
 Type: Single Stage
 Ignition Type: Intermittent Pilot
 Type of Gas: Natural
 Inlet/Outlet Size (in.): 3/4 in. x 3/4 in.
 Body Pattern: Straight-through
 Opening Characteristics: Standard
 Capacity @ 1 in. p.d.: 300,000 BTU/hr; 30,000 BTU/hr minimum
 Pressure Ratings (psi): 1/2 psi
 Pressure Ratings (kPa): 3.5 kPa
 Pressure Regulator Setting (psi): 3.5 in. wc
 Pressure Regulator Setting (kPa): 0.87 kPa
 Pilot Gas Outlet: Compression fitting for 1/4 in. OD tubing
 Pressure Tapping: 1/8 in. NPT with plug
 Electrical Connections: 1/4 in. quick-connect male terminals
 Electrical Ratings: 24 Vac
 Frequency: 60 Hz
 Anticipator Setting: 0.7 A
 Temperature Range (F): -40 F to +175 F
 Temperature Range (C): -40 C to +79 C
 Mounting: 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically
 Dimensions (in.): 5 3/8 in. high x 4 1/16 in. wide x 2 11/16 in. deep
 Dimensions (mm): 135 mm high x 104 mm wide x 69 mm deep
 Includes: Two 3/4 in. x 1/2 in. reducer bushing; 393691 Natural to LP gas conversion kit
 Approvals, American Gas Association IAS: AGA Design Certified: File No. L2025007
 Approvals, Canadian Gas Association: CGA Design Certified: File No. L2025007
 Approvals, Underwriters Laboratories Inc: UL Component Recognized 
Specs
Fuel Type:
Natural Gas
Gas Type:
Natural Gas
Body Pattern:
Straight-Through
Voltage:
24v
Capacity (BTU):
300000
Inlet Size:
3/4"
Outlet Size:
3/4"
Ignition Type:
Intermittent Pilot